CE Conformity

Accel/Decel Selection
The Accel/Decel rate can be obtained by a variety of methods. The default rate is
determined by
P041
[Accel Time 1] and
Accel/Decel rates can be made through digital inputs, communications and/or
parameters. See below for the override priority.
Purge Input Enabled
AND Active
Terminal Block Jog
Input Enabled AND
Active
Input(s) is
programmed as
Acc/Dec
(2/3/4)
Is speed controlled
by [Preset Freq x]
Active
[Speed Referencex]
= Comms
Active
[Speed Referencex]
= 13 (Step Logic)
Drive uses Accel 1
and Decel 1.
Compliance with the Low Voltage Directive and Electromagnetic Compatibility
Directive has been demonstrated using harmonized European Norm (EN)
standards published in the Official Journal of the European Communities.
PowerFlex 525 drives comply with the EN standards listed below when installed
according to the installation instructions in this manual.
CE Declarations of Conformity are available online at:
http://www.rockwellautomation.com/products/certification/.
Rockwell Automation Publication 520-UM001A-EN-E - February 2013
P042
[Decel Time 1]. Alternative
Accel/Decel always
Yes
Accel/Decel 1.
No
Drive stopped
Yes
(NOT running)
No
No
Accel/Decel 2 is active
Yes
when input is selected
by Accel and Decel input.
No
Accel/Decel 1/2/3/4 is
Yes
selected by the default
[Preset Freq x] setting.
No
Accel/Decel 1 or 2 is
Yes
selected according
to Comms.
No
Accel/Decel 1/2/3/4 is
Yes
selected according to
Step Logic
No
Installation/Wiring
Chapter 1
Accel/Decel from
Yes
[Jog Acc/Dec].
41