Appendix A
Supplemental Drive Information
148
PowerFlex 525 Estimated Watts Loss (Rated Load, Speed & PWM)
Voltage
Output Current (A)
380...480V,
1.4
50/60 Hz 3-Phase
2.3
4.0
6.0
10.5
13.0
17.0
24.0
30.0
380...480V,
1.4
50/60 Hz 3-Phase
2.3
w/ EMC Filter
4.0
6.0
10.5
13.0
17.0
24.0
30.0
37.0
43.0
525...600V,
0.9
50/60 Hz 3-Phase
1.7
3.0
4.2
6.6
9.9
12.0
19.0
22.0
27.0
32.0
Rockwell Automation Publication 520-UM001A-EN-E - February 2013
Total Watts Loss
27.0
37.0
80.0
86.0
129.0
170.0
221.0
303.0
387.0
27.0
37.0
81.0
88.0
133.0
175.0
230.0
313.0
402.0
602.0
697.0
22.0
32.0
50.0
65.0
95.0
138.0
164.0
290.0
336.0
466.0
562.0