Allen-Bradley PowerFlex 525 User Manual page 111

Adjustable frequency ac drive
Hide thumbs Also See for PowerFlex 525:
Table of Contents

Advertisement

A531 [Start Boost]
Sets the boost voltage (% of
P031
[Motor NP Volts]) and redefines the V/Hz curve when
[Maximum Voltage]
[Motor NP Volts]
[Break Frequency]
[Minimum Freq]
Values
Default:
Min/Max:
Display:
A532 [Break Voltage]
Sets the voltage (in percent of [Base Frequency]) at the
Values
Default:
Min/Max:
Display:
A533 [Break Frequency]
Sets the frequency where
A532
[Break Voltage] is applied if
Values
Default:
Min/Max:
Display:
A534 [Maximum Voltage]
Sets the highest voltage the drive outputs.
Values
Default:
Min/Max:
Display:
Advanced Program Group (continued)
Frequency
[Motor NP Hertz]
[Maximum Freq]
2.5%
0.0/25.0%
0.1%
A533
[Break Frequency] if
A530
25.0%
0.0/100.0%
0.1%
A530
[Boost Select] is set to 0 "Custom V/Hz".
15.0 Hz
0.0/500.0 Hz
0.1 Hz
Drive Rated Volts
20/Drive Rated Volts
1V
Rockwell Automation Publication 520-UM001A-EN-E - February 2013
A530
[Boost Select] = 0 "Custom V/Hz" and
[Boost Select] is set to 0 "Custom V/Hz".
Programming and Parameters
Related Parameter(s): P031, P032, P039,
P039
[Torque Perf Mode] = 0 "V/Hz".
Related Parameter(s): P031, P032, P039, A530,
Related Parameter(s): P031, P032, P039, A530,
Related Parameter(s):
Chapter 3
A530
A533
A532
b004
111

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents