the overall drive performance. Unless specified in the individual distance tables as
tested with the drive, these cables are not recommended and their performance
against the lead length limits supplied is not known.
Recommended Shielded Wire
Location
Rating/Type
Standard (Option 1) 600V, 90 °C (194 °F) XHHW2/RHW-2
Anixter B209500-B209507, Belden
29501-29507, or equivalent
Standard (Option 2) Tray rated 600V, 90 °C (194 °F)
RHH/RHW-2 Anixter OLF-7xxxxx or
equivalent
Tray rated 600V, 90 °C (194 °F)
Class I & II;
Division I & II
RHH/RHW-2 Anixter 7V-7xxxx-3G or
equivalent
Reflected Wave Protection
The drive should be installed as close to the motor as possible. Installations with
long motor cables may require the addition of external devices to limit voltage
reflections at the motor (reflected wave phenomena). Refer to Reflected Wave in
"Wiring and Grounding Guide, (PWM) AC Drives, " publication
IN001.
The reflected wave data applies to all carrier frequencies 2...16 kHz.
For 240V ratings and lower, reflected wave effects do not need to be considered.
Output Disconnect
The drive is intended to be commanded by control input signals that will start
and stop the motor. A device that routinely disconnects then reapplies output
power to the motor for the purpose of starting and stopping the motor should
not be used. If it is necessary to disconnect power to the motor with the drive
outputting power, an auxiliary contact should be used to simultaneously disable
drive (Aux Fault or Coast to Stop).
Rockwell Automation Publication 520-UM001A-EN-E - February 2013
Description
• Four tinned copper conductors with XLPE insulation.
• Copper braid/aluminum foil combination shield and
tinned copper drain wire.
• PVC jacket.
• Three tinned copper conductors with XLPE insulation.
• 5 mil single helical copper tape (25% overlap min.)
with three bare copper grounds in contact with shield.
• PVC jacket.
• Three bare copper conductors with XLPE insulation
and impervious corrugated continuously welded
aluminum armor.
• Black sunlight resistant PVC jacket overall.
• Three copper grounds on #10 AWG and smaller.