Chapter 3
Programming and Parameters
t069 [Opto Out1 Sel]
t072 [Opto Out2 Sel]
Determines the operation of the programmable digital outputs.
Options
Setting Output Changes State When...
0 "Ready/Fault"
Opto outputs are active when power is applied. Indicates that the drive is ready for operation. Opto outputs are
inactive when power is removed or a fault occurs.
1 "At Frequency"
Drive reaches commanded frequency.
2 "MotorRunning"
Motor is receiving power from the drive.
3 "Reverse"
Drive is commanded to run in reverse direction.
4 "Motor Overld"
Motor overload condition exists.
5 "Ramp Reg"
Ramp regulator is modifying the programmed accel/decel times to avoid an overcurrent or overvoltage fault from
occurring.
6 "Above Freq"
Drive exceeds the frequency (Hz) value set in
7 "Above Cur"
Drive exceeds the current (% Amps) value set in
8 "Above DCVolt"
Drive exceeds the DC bus voltage value set in
9 "Retries Exst"
Value set in
10 "Above Anlg V"
Analog input voltage (0-10V input) exceeds the value set in
11 "Above PF Ang"
Power Factor angle exceeds the value set in
12 "Anlg In Loss"
Analog input loss has occurred. Program
input loss occurs.
13 "ParamControl"
Output is directly controlled by the state of the
turn off. A value of 1 or greater in this parameter causes the output to turn on.
14 "NonRec Fault"
• Value set in
• A non-resettable fault has occurred.
15 "EM Brk Cntrl"
EM Brake is energized. Program
16 "Thermal OL"
Relay energizes when thermal Motor overload counter is above the value set in
also energizes if the drive is within 5 °C of the drive overheat trip point.
17 "Amb OverTemp"
Relay energizes when control module over temperature occurs.
18 "Local Active"
Active when drive P046,
19 "Comm Loss"
Active when communication is lost from any comm source with reference or control.
20 "Logic In 1"
An input is programmed as "Logic Input 1" and is active.
21 "Logic In 2"
An input is programmed as "Logic Input 2" and is active.
22 "Logic 1 & 2"
Both Logic inputs are programmed and active.
23 "Logic 1 or 2"
One or both Logic inputs are programmed and one or both is active.
24 "StpLogic Out"
Drive enters StepLogic step with Command Word set to enable Logic output.
25 "Timer Out"
Timer has reached the value set in
26 "Counter Out"
Counter has reached the value set in
27 "At Position"
Drive is in Positioning mode and has reached the commanded position. Tolerance is adjusted with
Pos Tol].
28 "At Home"
Drive is in Positioning mode and has reached the home position. Tolerance is adjusted with
29 "Safe-Off"
Both safe-off inputs are active.
Values
Default:
Opto Out1 Sel:
Opto Out2 Sel:
Min/Max:
Display:
76
Terminal Block Group (continued)
ì
Value for t070 or t073 [Opto Outx Level] must be entered in percent of drive rated output
IMPORTANT
current.
A541
[Auto Rstrt Tries] is exceeded.
IMPORTANT
Do not use if
t093
A541
[Auto Rstrt Tries] is exceeded or
A541
[Auto Rstrt Tries] is not enabled or
t087
[EM Brk On Delay] and
P048
or
P050
[Start Source x] is in local keypad control.
t070
or
t070
2
1
0/29
1
Rockwell Automation Publication 520-UM001A-EN-E - February 2013
t070
or
t073
[Opto Outx Level].
t070
or
t073
[Opto Outx Level].
t070
or
t073
[Opto Outx Level].
t070
or
t073
[Opto Outx Level].
[10V Bipolar Enbl] is set to 1 "Bi-Polar In".
t070
or
t073
[Opto Outx Level].
t094
[Anlg In V Loss] or
t097
[Anlg In mA Loss] for desired action when
t070
or
t073
[Opto Outx Level]. A value of 0 causes the output to
t086
[EM Brk Off Delay] for desired action.
t077
t073
[Opto Outx Level] or not timing.
or
t073
[Opto Outx Level] or not counting.
Related Parameter(s): P046, P048, P050, t070, t073, t077, t082,
t086, t087, t093, t094, t097, A541,
Hysteresis
None
0.5 Hz above; 1.0 Hz below
None
None
100 ms time delay on or off
100 ms time delay on or off
100 ms time delay on or off
100 ms time delay on or off
100 ms time delay on or off
None
100 ms time delay on or off
100 ms time delay on or off
On, 2 mA / ±1V
Off, 3 mA / ±1.5V
None
None
None
or
t082
[Relay Outx Level]. It
None
None
None
None
None
None
None
None
None
None
None
A564
[Encoder
A564
[Encoder Pos Tol]. –
A564