Chapter 3
Programming and Parameters

Basic Program Group

P030 [Language]
Selects the language displayed. A reset or power cycle is required after selection is made.
Options
1 English (Default)
2 Français
3 Español
4 Italiano
5 Deutsch
6 Japanese
7 Português
8 Chinese
9 Reserved
10 Reserved
11 Korean
12 Polish
13 Reserved
14 Turkish
15 Czech
P031 [Motor NP Volts]
Stop drive before changing this parameter.
Sets the motor nameplate rated volts.
Values
Default:
Min/Max:
Display:
P032 [Motor NP Hertz]
Stop drive before changing this parameter.
Sets the motor nameplate rated frequency.
Values
Default:
Min/Max:
Display:
P033 [Motor OL Current]
Sets the motor nameplate overload current. Used to determine motor overload conditions and can be set from 0.1 A to 200% of drive rated current.
IMPORTANT
The drive will fault on an F007 "Motor Overload" if the value of this parameter is exceeded by 150% for 60 s.
Values
Default:
Min/Max:
Display:
P034 [Motor NP FLA]
Sets the motor nameplate FLA. Used to assist the Autotune routine and motor control.
Values
Default:
Min/Max:
Display:
68
Chinese Simplified
Based on Drive Rating
10 (for 200V Drives), 20 (for 400V Drives), 25 (for 600V Drives)/Drive Rated Volts
1V
60 Hz
15/500 Hz
1 Hz
Based on Drive Rating
0.0/(Drive Rated Amps x 2)
0.1 A
Drive Rated Amps
0.0/(Drive Rated Amps x 2)
0.1 A
Rockwell Automation Publication 520-UM001A-EN-E - February 2013
Language Support
HIM/LCD Display
RSLogix 5000/
Logix Designer
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Related Parameter(s): b004, A530, A531, A532,
Related Parameter(s): A493, A530, A531, A532,
Related Parameter(s): t069, t072, t076, t081, A484, A485,
Related Parameter(s):
Connected
Components
Workbench
Y
Y
Y
Y
Y
Y
A533
A533
A493
P040