Appendix D
Velocity StepLogic, Basic Logic and Timer/Counter Functions
186
Digit 2 – Defines what logic must be met to jump to a step other than the very next step.
Setting
Description
0
Skip Step (jump immediately)
1
Step based on the time programmed in the respective [Stp Logic Time x] parameter.
2
Step if "Logic In 1" is active (logically true)
3
Step if "Logic In 2" is active (logically true)
4
Step if "Logic In 1" is not active (logically false)
5
Step if "Logic In 2" is not active (logically false)
6
Step if either "Logic In 1" or "Logic In 2" is active (logically true)
7
Step if both "Logic In 1" and "Logic In 2" is active (logically true)
8
Step if neither "Logic In 1" or "Logic In 2" is active (logically true)
9
Step if "Logic In 1" is active (logically true) and "Logic In 2" is not active (logically false)
A
Step if "Logic In2" is active (logically true) and "Logic In 1" is not active (logically false)
b
Step after [Stp Logic Time x] and "Logic In 1" is active (logically true)
C
Step after [Stp Logic Time x] and "Logic In 2" is active (logically true)
d
Step after [Stp Logic Time x] and "Logic In 1" is not active (logically false)
E
Step after [Stp Logic Time x] and "Logic In 2" is not active (logically false)
F
Do not step OR no "jump to", so use Digit 0 logic
Digit 1 – Defines what logic must be met to jump to the very next step.
Setting
Description
0
Skip Step (jump immediately)
1
Step based on the time programmed in the respective [Stp Logic Time x] parameter.
2
Step if "Logic In 1" is active (logically true)
3
Step if "Logic In 2" is active (logically true)
4
Step if "Logic In 1" is not active (logically false)
5
Step if "Logic In 2" is not active (logically false)
6
Step if either "Logic In 1" or "Logic In 2" is active (logically true)
7
Step if both "Logic In 1" and "Logic In 2" is active (logically true)
8
Step if neither "Logic In 1" or "Logic In 2" is active (logically true)
9
Step if "Logic In 1" is active (logically true) and "Logic In 2" is not active (logically false)
A
Step if "Logic In 2" is active (logically true) and "Logic In 1" is not active (logically false)
b
Step after [Stp Logic Time x] and "Logic In 1" is active (logically true)
C
Step after [Stp Logic Time x] and "Logic In 2" is active (logically true)
d
Step after [Stp Logic Time x] and "Logic In 1" is not active (logically false)
E
Step after [Stp Logic Time x] and "Logic In 2" is not active (logically false)
F
Use logic programmed in Digit 1

Rockwell Automation Publication 520-UM001A-EN-E - February 2013

Logic
SKIP
TIMED
TRUE
TRUE
FALSE
FALSE
OR
AND
NOR
XOR
XOR
TIMED AND
TIMED AND
TIMED OR
TIMED OR
IGNORE
Logic
SKIP
TIMED
TRUE
TRUE
FALSE
FALSE
OR
AND
NOR
XOR
XOR
TIMED AND
TIMED AND
TIMED OR
TIMED OR
IGNORE