Setting Example
1 second min.
In this example, let's set the parameters as follows:

"input type"

"scaling upper limit value" = "950"
"scaling lower limit value" = "100"
"decimal point"
(1) Select the menu display, and select [
or
keys. For details on selecting the menu display, see page
1-8.
(2) Press the
key to enter the setup mode. The top parameter in the
setup mode [
is "2".
(3) Press the
key until the display indicates "17".
(4) Press the
key to fix the set value. The display changes to [
("scaling upper limit value" parameter). The parameter default is
"100".
(5) Press the
key until the display indicates "950".
(6) Press the
key to fix the set value. The display changes to [
("scaling lower limit value" parameter). The parameter default is "0".
(7) Press the
key until the display indicates "100".
(8) Press the
key to fix the set value. The display changes to [
("decimal point" parameter). The parameter default is "0".
(9) Press the
key until the display indicates "1".
3.2 Setting Input Specifications
= "17 (4 to 20 mA)"
= "1"
] "input type" is displayed. The parameter default
] (setup mode) using the
3--5
]
]
]