Remote PAUSE

Change the C Controller module status to PAUSE externally while the RESET/STOP/RUN switch is on the RUN position. Use
this function to retain the output (Y) of the C Controller module in the RUN state in such system as process control.
Executing remote operations
The following methods are available to execute remote PAUSE:
■Using CW Configurator
Refer to the following manual.
CW Configurator Operating Manual
■Using a user program
Execute the C Controller module dedicated function (CCPU_Control) to perform remote PAUSE.
MELSEC iQ-R C Controller Module Programming Manual
■Using SLMP
Refer to the following manual.
SLMP Reference Manual
Precautions
The user program does not stop executing even if the C Controller module is in the remote PAUSE state. To change the
processing according to the operating status of the C Controller module, use the C Controller module dedicated function
(CCPU_GetCpuStatus) in the program.
Remote RESET
Reset the C Controller module externally while the module is in the STOP state (including the case in which the module is
stopped due to an error). Even when the RESET/STOP/RUN switch is on the RUN position, the C Controller module can be
reset while the module is in STOP state.
Enabling remote RESET
Before performing remote RESET, enable the remote RESET.
[CPU Parameter]  [Operation Related Setting]  [Remote Reset Setting]
Window
Displayed items
Item
Remote Reset
4 BASIC FUNCTIONS
40
4.3 Remote Operation Function
Description
Set whether to enable remote RESET.
Setting range
Default
• Disable
Disable
• Enable