CHAPTER 4: COMMUNICATION
 
 
 

4.1.12 Modbus Register Map

 
Function Code 03 - Read Holding Registers Function Code 06
- Write Holding Registers Function Code 16 Write Multiple Holding Registers
 
 
 
Holding
Modbus
Register
Size
 
 
 
16 bit
Basic Parameter Setting
 
Bit0 -
 
 
0 = (0-20mA) Analog Output selected
 
1 = (4 - 20mA) ] - Analog Output selected
 
Bit1 - [ 0 - OFF, 1 - ON] -- Overload Memory
 
 
 
 
 
 
 
 
 
Bit2 - [ 0 - Immediate , 1 - Delayed] - Max
 
Current
5
Bit3 - Free
 
Bit4 - Debug Mode
 
0 = OFF
1 - ON -
Bit5, Bit6 - Phase Selection
 
00 => 3-Phase
01 => 2-Phase (Bit5 = 1, Bit6 = 0)
10 => 1-Phase (Bit5 = 0, Bit6 = 1)
Bit7 - TwoSpeedMotor
 
6
16 bit
Bus Failure Behavior
bit0 - bit 3
1 - Ignore - Profibus Class1 Failure
2 - Delayed OFF
3 - Delayed ON1
4 - Delayed ON2
bit 4 - bit 7
1 - Ignore - Modbus Failure
2 - Delayed OFF
3- Delayed ON1
4- Delayed ON2
12
16 bit
Overload Delay
1 - Class5
2 - Class10
3 - Class15
4 - Class20
5 - Class25
6 - Class30
7 - Class35
8 - Class40
13
16 bit
Overload Cooling Constant
14
16 bit
Ground Fault Pick-Up
4.17
 
Variable
 
Selection of Analog Output type
1 means use store data in EEProm:
- Trip condition -(trip or not for LT and
Thermistor) - if trip condition is set in
EEProm, motor cannot be started until
the motor is cooled and warning or fault
is reset.
Reset cooling:
- FC 06 register 13 set to zero
- FC 05 register 144
0 means do not use EEPROM data - no faults or
warnings are saved upon power down
0 = perform max current monitoring
immediately
1= delayed the max current monitoring by 2
minutes (after motor start)
Debug mode = ON
- Additional Profibus DP telegram will be
available:
V4 retrofit = telegram B2721
V5 = telegram B40005
Number of phase selection
Type of motor selection
0 - disable
1 - enable (use for pole changer and
Dahlander typicals)
Behavior of the EntelliPro ES upon
Communication Bus Failure
 
Delay Motor stop
Delay Motor forward ON
Delay Motor reverse ON
 
 
Delay Motor stop
Delay Motor forward ON
Delay Motor reverse ON
Overload Trip Class selection
Cooling algorithm selection
0 = No thermal memory
 
Description
Min
0
 
 
 
 
 
 
0
1
0
2
EP OS MOTOR MANAGEMENT SY STEM – INSTRUCTION MANUAL
 
 
 
Max
Step
Units
Scale
 
 
 
255
1
n/a
n/a
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
255
1
n/a
n/a
8
1
n/a
n/a
15
1
n/a
n/a
8
1
%
GF PU
Setting
x 10
2 = 20%
Format Default
Unsigned
6
Integer
 
 
 
 
 
 
 
 
 
 
 
 
Unsigned
1
Integer
Unsigned
1
Integer
Unsigned
15
Integer
Unsigned
2
Integer