CHAPTER 5: SETTINGS
unreturned messages. This function counts all the outgoing messages and a separate counter adds the messages have
failed to return. When the unreturned messages counter reaches the user-definable level specified by the
setting and within the user-defined message count
ALARM CH1 THRESHOLD
FlexLogic operand is set.
UNRET ALM
When the total message counter reaches the user-defined maximum specified by the
setting, both the counters reset and the monitoring process is restarted.
COUNT
Configure the operand to drive an output contact, user-programmable LED, or selected communication-based output.
Latching and acknowledging conditions, if required, are programmed accordingly.
The unreturned messages alarm function is available on a per-channel basis and is active only in the ring configuration.
The total number of unreturned input and output messages is available as the
 UNRETURNED MSG COUNT CH1

5.3.17 Installation

SETTINGS  PRODUCT SETUP  INSTALLATION
 INSTALLATION
To safeguard against the installation of a relay without any entered settings, the unit does not allow signaling of any
output relay until
RELAY SETTINGS
PROGRAMMED self-test error message displays until the relay is put into the "Programmed" state.
The
setting allows the user to uniquely identify a relay. This name appears on generated reports.
RELAY NAME

5.4 Remote resources

5.4.1 Remote resources configuration

When the C70 is ordered with a process card module as a part of HardFiber system, an additional Remote Resources
menu tree is available in the EnerVista software to allow configuration of the HardFiber system.
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
actual value.
RELAY SETTINGS:
Not Programmed
RELAY NAME:
Relay-1
is set to "Programmed." This setting is "Not Programmed" by default. The UNIT NOT
Figure 5-46: Remote Resources configuration menu
REMOTE RESOURCES
UNRET MSGS ALARM CH1 COUNT
UNRET MSGS ALARM CH1 MESSAGE
ACTUAL VALUES  STATUS  DIRECT INPUTS
Range: Not Programmed, Programmed
Range: up to 20 alphanumeric characters
UNRET MSGS
, the
DIR IO CH1
5