GE C70 Instruction Manual page 186

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

PRODUCT SETUP
conf-revision
Notice that OptFlds bits buffer-overflow and entryID are not applicable to unbuffered reports even though the bits exist
in the protocol. They are therefore labelled N/A (not applicable) on the display.
Unbuffered Report1 BufTm
Range: 0 to 4294967295 in steps of 1
Default: 0
The entered value sets the time interval in milliseconds for the buffering of events for inclusion into a single report.
Unbuffered Report1 TrgOps
Range: The check box for an individual bit can be enabled or not
Default: All bits true
The TrgOps setting is bitstring that controls which trigger conditions are monitored in this report. The options are as
follows:
data-change
quality-change
integrity
general interrogation
Unbuffered Report1 IntgPd
Range: 0 to 4294967295 in steps of 1.
Default: 0
The entered value sets the period in milliseconds for generating Unbuffered Report1 integrity reports. An integrity report
includes the values of all members of the referenced data set, whether a change has occurred or not.
5
DataSets
Navigate to Settings > Product Setup > Communications > IEC 61850 > DataSets.
As mentioned in the preceding GOOSE and Reports sections, the members whose values are communicated by these
services are itemized in an ordered list known as a data set. Each UR with the IEC 61850 option has 12 data sets. Each data
set can contain as many as 64 members. Any data set can be used simultaneously by any number of TxGOOSE elements
and/or by any number of Configurable Report elements. UR Setup software can configure any FlexLogic operands and any
FlexAnalog operands as members.
UR Setup requires data set members to be IEC 61850 data objects or data attributes with Functional Constraint ST or MX.
Certain FlexLogic and FlexAnalog operands have factory assigned data attributes as tabulated in the UR Series
Communications Guide. All FlexLogic and FlexAnalog operands can be user-assigned to GGIO1 or GGIO4 data attributes,
so that operands without factory assigned data attributes can still have their values published. See the GGIO1 and GGIO4
sections later for details.
5-62
Figure 5-20: IEC 61850 DataSets
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS