GE C70 Instruction Manual page 103

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

CHAPTER 4: INTERFACES
Once the template has been applied, users are limited to view and edit the FlexLogic entries not locked by the template.
The effect of applying the template to the FlexLogic entries is shown here.
Figure 4-9: Locking FlexLogic entries through settings templates
Typical FlexLogic™ entries without template applied.
The FlexLogic entries are also shown as locked in the graphical view and on the front panel display.
4.1.7.2 Lock FlexLogic equations to the serial number
A settings file and associated FlexLogic equations also can be locked to a UR serial number. Once FlexLogic entries in a
settings file have been secured, use the following procedure to lock the settings file to a serial number.
1.
Right-click the setting file in the offline window area and select the Edit Settings File Properties item. The window
opens.
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Figure 4-10: Secured FlexLogic in graphical view
ENERVISTA SOFTWARE INTERFACE
Typical
FlexLogic™ entries
locked with template via
the
Template Mode > View In Template Mode
command.
842861A1.CDR
4-9