PRODUCT SETUP
Message delivery time is approximately 0.2 of power system cycle (at 128 kbps) times number of 'bridges' between the
origin and destination. Dual-ring configuration effectively reduces the maximum 'communications distance' by a factor of
two.
In this configuration the following delivery times are expected (at 128 kbps) if both rings are healthy:
IED 1 to IED 2: 0.2 of power system cycle
IED 1 to IED 3: 0.4 of power system cycle
IED 1 to IED 4: 0.2 of power system cycle
IED 2 to IED 3: 0.2 of power system cycle
IED 2 to IED 4: 0.4 of power system cycle
IED 3 to IED 4: 0.2 of power system cycle
If one ring is broken (say TX2-RX2) the delivery times are as follows:
IED 1 to IED 2: 0.2 of power system cycle
IED 1 to IED 3: 0.4 of power system cycle
IED 1 to IED 4: 0.6 of power system cycle
IED 2 to IED 3: 0.2 of power system cycle
IED 2 to IED 4: 0.4 of power system cycle
IED 3 to IED 4: 0.2 of power system cycle
A coordinating timer for this bus protection scheme could be selected to cover the worst case scenario (0.4 of a power
system cycle). Upon detecting a broken ring, the coordination time is adaptively increased to 0.6 of a power system cycle.
The complete application requires addressing a number of issues, such as failure of both the communications rings, failure
or out-of-service conditions of one of the relays, and so on. Self-monitoring flags of the direct inputs and outputs feature
primarily are used to address these concerns.
Example 3: Pilot-aided schemes
5
Consider the three-terminal line protection application shown.
A permissive pilot-aided scheme can be implemented in a two-ring configuration, shown as follows (IEDs 1 and 2
constitute a first ring, while IEDs 2 and 3 constitute a second ring).
5-108
Figure 5-43: Three-terminal line application
UR IED 1
Figure 5-44: Single-channel open loop configuration
TX1
UR IED 1
RX1
UR IED 3
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
UR IED 2
UR IED 3
842713A1.CDR
RX1
RX2
UR IED 2
TX1
TX2
RX1
TX1
842714A1.CDR
CHAPTER 5: SETTINGS