GE C70 Instruction Manual page 155

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
EnerVista Software
5.3.4.4 Network
As outlined in the previous section, when using more than one Ethernet port, configure each to belong to a different
network or subnet using the IP addresses and mask. Configure the network IP and subnet settings before configuring the
routing settings.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  NETWORK 1(3)
 NETWORK PORT 1
 NETWORK PORT 2
 NETWORK PORT 3
The IP addresses are used with the DNP, Modbus/TCP, IEC 61580, IEC 60870-5-104, TFTP, HTTP, and PRP protocols. PRP is
explained in its own section later.
— This setting sets the port's IPv4 address in standard IPV4 format. This setting is valid on port 3 if
PRT1 (2 or 3) IP ADDRESS
port 2
is set to None.
REDUNDANCY
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Figure 5-7: Multiple LANS, no redundancy
Public Network
LAN1
LAN2
ML3000
ML3000
P1
P2
IP1/
IP2/
MAC2
MAC1
UR
PRT1 IP ADDRESS:
127.0.0.1
PRT1 SUBNET IP MASK:
255.0.0.0
PRT2 IP ADDRESS:
127.0.0.1
PRT2 SUBNET IP MASK:
255.0.0.0
PRT2 REDUNDANCY:
None
PRT2 PRP MCST ADDR:
01-15-4E-00-01-00
PRT3 IP ADDRESS:
127.0.0.1
PRT3 SUBNET IP MASK:
255.0.0.0
SCADA
LAN3
ML3000
P3
IP3/
MAC3
859710A2.vsd
Range: standard IPV4 address format
Range: standard IPV4 address format
Range: standard IPV4 address format
Range: standard IPV4 address format
Range: None, Failover, PRP
Range if no PRP license: None, Failover
Range: 01-15-4E-00-01-00 to 01-15-4E-00-01-FF
Range: standard IPV4 address format
Range: standard IPV4 address format
PRODUCT SETUP
5
5-31