TARGETS MENU
•
The faceplate In Service LED indicator turns off
•
A RELAY OUT OF SERVICE event is recorded
7.2.2.2 Major self-test error messages
The major self-test errors are outlined in this section.
INCOMPATIBLE H/W:
Contact Factory (xxx)
•
Latched target message: Yes.
•
Description of problem: One or more installed hardware modules is not compatible with the C70 order code.
•
How often the test is performed: Module dependent.
•
What to do: Contact the factory and supply the failure code noted in the display. The "xxx" text identifies the failed
module (for example, F8L).
EQUIPMENT MISMATCH:
with 2nd line detail
•
Latched target message: No.
•
Description of problem: The configuration of modules does not match the order code stored in the C70.
•
How often the test is performed: On power up. Afterwards, the backplane is checked for missing cards every five
seconds.
•
What to do: Check all modules against the order code, ensure they are inserted properly, and cycle control power. If
the problem persists, contact the factory.
FLEXLOGIC ERROR:
with 2nd line detail
•
Latched target message: No.
•
Description of problem: A FlexLogic equation is incorrect.
•
How often the test is performed: The test is event driven, performed whenever FlexLogic equations are modified
•
What to do: Finish all equation editing and use self tests to debug any errors.
UNIT NOT PROGRAMMED:
Check Settings
7
•
Latched target message: No.
•
Description of problem: The
programmed.
•
How often the test is performed: On power up and whenever the
setting is altered
•
What to do: Program all settings and then set
7.2.2.3 Minor self-test error messages
Most of the minor self-test errors can be disabled. See the settings in the User-programmable Self-tests section in chapter
5.
MODULE FAILURE___:
Contact Factory (xxx)
•
Latched target message: Yes.
•
Description of problem: Module hardware failure detected.
•
How often the test is performed: Module dependent.
7-10
PRODUCT SETUP INSTALLATION RELAY SETTINGS
.
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP INSTALLATION RELAY SETTINGS
PRODUCT SETUP INSTALLATION RELAY SETTINGS
CHAPTER 7: COMMANDS AND TARGETS
setting indicates the C70 is not
to "Programmed."
.