LOGIC DIAGRAMS

4.3 Logic diagrams
Logic diagrams in this instruction manual provide an overview of function and settings. A logic diagram is based on
Inputs-on the left side, which are setting and operands
Logical gates, which is Boolean algebra to combine logical lines using AND, OR, NOT, and other gates to get a new
logical state
Logical operators, which are timers, one-shot operations, latches, and so on
Outputs-on the right side, which are products of the manipulations with inputs, logical gates, and logical operators to
produce new operands and define the output state of the element
True and false values are denoted by 1 and 0 respectively. A function usually is high/on/enabled when 1.
Reading from right to left in the following diagram, the
are triggered when either the settings or reset latch in the middle of the diagram is triggered. When this applies, the
operand is triggered after the delay set by the
BUS 1 OP
operand initiates immediately. The settings or reset latch in the middle of the diagram is triggered as follows.
TRIP BUS 1 PKP
For the reset, one of three conditions are required to meet the OR requirement shown at the bottom left. That is, the
TRIP BUS 1 LATCHING
4
from the
TRIP BUS 1 RESET
For the settings, one of 16 input conditions at the top left must be met for the OR, the
Enabled, and the
Table 4-1: Logic diagram symbols
Symbol
Description
= Off
Output from FlexLogic operand, so user-defined
= Enabled
1 = Enabled and 0 = Disabled
OR
Any function input on the left side satisfies the condition
AND
All functions input on the left side are required to satisfy the condition
Not. Negates/reverses the output, for example 0 becomes 1.
Connection
S, R
Set, Reset
T
Timer pickup. Triggered by the settings latch in the diagram.
PKP
T
Timer reset. Triggered by the reset latch in the diagram.
RST
4-28
setting must be 0=Disabled (which is negated by the NOT function to become 1=Enabled), output
FlexLogic operand must be 1, or output from the
output must output as 0, which is then negated/reversed by NOT to become 1.
TRIP BUS 1 BLOCK
Figure 4-25: Logic diagram
SETTINGS
TRIP BUS 1 INPUT 1
= Off
TRIP BUS 1 INPUT 2
= Off
OR
TRIP BUS 1 INPUT 16
= Off
SETTINGS
TRIP BUS 1
FUNCTION
= Enabled
TRIP BUS 1 BLOCK
AND
= Off
SETTINGS
TRIP BUS 1
LATCHING
= Enabled
TRIP BUS 1 RESET
= Off
OR
FLEXLOGIC OPERAND
RESET OP
and
TRIP BUS 1 OP
TRIP BUS 1 PKP
TRIP BUS 1 PICKUP DELAY
SETTINGS
TRIP BUS 1 PICKUP
DELAY
Non-volatile,
TRIP BUS 1 RESET
set-dominant
DELAY
AND
S
T
PKP
Latch
R
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
CHAPTER 4: INTERFACES
FlexLogic operands on the right side
or
setting, while the
TRIP BUS 1 RESET DELAY
FlexLogic operand must be 1.
RESET OP
TRIP BUS 1 FUNCTION
FLEXLOGIC OPERAND
TRIP BUS 1 OP
T
RST
FLEXLOGIC OPERAND
TRIP BUS 1 PKP
842023A1.CDR
TRIP
must be