CONNECT TO THE C70
5.
Select the Serial interface and the correct COM Port, then click Connect.
6.
The EnerVista UR Setup software creates a site named "Quick Connect" with a corresponding device also named
3
"Quick Connect" and displays them on the left side of the screen. Expand the sections to view data directly from the
C70 device. Use the Device Setup button to change the site names.
Each time that the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct
communications to the C70. This ensures that configuration of the EnerVista UR Setup software matches the C70 model
number.

3.8.3 Use Quick Connect via a rear Ethernet port

To use the Quick Connect feature to access the C70 from a computer through Ethernet, first assign an IP address to the
relay using the front panel keyboard.
1.
Press the
MENU
2.
Navigate to
Settings  Product Setup  Communications  Network  IP Address Setting
3.
Enter an IP address, for example "1.1.1.1," and press the
4.
In the same menu, select the
5.
Enter a subnet IP address, for example "255.0.0.0," and press the
Next, use an Ethernet cross-over cable to connect the computer to the rear Ethernet port. In case you need it, the
following figure shows the pinout for an Ethernet cross-over cable.
3 4 5 6
2
1
Now, assign the computer an IP address compatible with the relay's IP address.
1.
From the Windows desktop, right-click the My Network Places icon and select Properties to open the network
3-44
Figure 3-52: Quick Connect window to access a device
key until the
menu displays.
Settings
setting.
Subnet IP Mask
Figure 3-53: Ethernet cross-over cable PIN layout
END 1
7
Pin
Wire color
8
1
White/orange
2
Orange
3
White/green
4
Blue
5
White/blue
6
Green
7
White/brown
8
Brown
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
key to save the value.
ENTER
key to save the value.
ENTER
END 2
Diagram
Pin
Wire color
1
White/green
2
Green
3
White/orange
4
Blue
5
White/blue
6
Orange
7
White/brown
8
Brown