CHAPTER 5: SETTINGS
RxGOOSE DSP1 DEFAULT STATE
Range: intermediate-state, off, on, bad-state, Latest
Default: Latest
This setting selects the logic state for the data attribute @Master/GGIO3.IndPos01.stVal when the UR has just completed
start-up and the selected RxGOOSE has not yet received a message, and when the RxGOOSE has lost its connectivity
with the publisher. When this setting is selected to Latest, the value of @Master/GGIO3.IndPosψψ.stVal is intermediate-
state when the UR has just completed start-up and the selected RxGOOSE has not yet received a message, and the
latest received value when the RxGOOSE loses its connectivity with the publisher.
RxGOOSE DPS1 EVENTS
Range: Disabled, Enabled
Default: Disabled
This setting selects whether Off to On transitions of the RxGOOSE DPS1 FlexLogic operands are recorded by the event
recorder. If set to Enabled, Off to On transitions are recorded. On to Off transitions are not recorded, even if events are
enabled.
RxGOOSE analog inputs
Navigate to Settings > Product Setup > Communications > IEC 61850 > GOOSE > RxGOOSE > RxGOOSE Analog Inputs >
RxGOOSE Analog Input1 to access the settings for the first RxGOOSE Boolean. The settings and functionality for the others
are similar.
RxGOOSE Analog1 ID
Range: 0 to 12 characters
Default: RxG Analog1
This setting allows the user to assign descriptive text to RxGOOSE Analog1. This descriptive text also appears in the SCL
files associated with the C70. Unlike RxGOOSE Booleans and RxGOOSE DPS, the RxGOOSE Analog operands have fixed
names, for example RxGOOSE Analog1.
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Figure 5-17: RxGOOSE Analog Inputs panel