GE C70 Instruction Manual page 303

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
5.7.4.5 Neutral current unbalance (ANSI 60N, IEC PVCB/PTOC)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  NEUTRAL CURRENT  NEUTRAL CURRENT
UNBALANCE 1(3)
 NEUTRAL CURRENT
 UNBALANCE 1
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Figure 5-85: Neutral directional overcurrent logic
NTRL CUR UNBALCE 1
FUNCTION: Disabled
NTRL CUR UNBALCE 1
BANK SOURCE: SRC 1
NTRL CUR UNBALCE 1
K MAG: 0.0000
NTRL CUR UNBALCE 1
K ANG: 0°
NTRL CUR UNBALCE 1
STG 1 PKP: 0.020 pu
NTRL CUR UNBALCE 1
STG 1 SLOPE: 2.0%
GROUPED ELEMENTS
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: 0.0000 to 0.1500 in steps of 0.0001
Range: 0 to 359° in steps of 1
Range: 0.001 to 5.000 pu in steps of 0.001
Range: 0.0 to 10.% in steps of 0.1