User-Programmable Elements - GE C70 Instruction Manual

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

SPECIFICATIONS
Timer accuracy:

2.5.2 User-programmable elements

FLEXLOGIC
Programming language:
Lines of code:
2
Internal variables:
Supported operations:
Inputs:
Number of timers:
Pickup delay:
Dropout delay:
FLEXCURVES™
Number:
Reset points:
Operate points:
Time delay:
FLEX STATES
Number:
Programmability:
FLEXELEMENTS™
Number of elements:
Operating signal:
Operating signal mode:
Operating mode:
Comparator direction:
Pickup Level:
Hysteresis:
Delta dt:
Pickup and dropout delay:
NON-VOLATILE LATCHES
Type:
Number:
Output:
Execution sequence:
USER-PROGRAMMABLE LEDs
Number:
Programmability:
Reset mode:
LED TEST
Initiation:
Number of tests:
Duration of full test:
Test sequence 1:
Test sequence 2:
Test sequence 3:
USER-DEFINABLE DISPLAYS
Number of displays:
2-22
±3% or 10 ms, whichever is greater
Reverse Polish Notation with graphical visualization (keypad programmable)
512
64
NOT, XOR, OR (2 to 16 inputs), AND (2 to 16 inputs), NOR (2 to 16 inputs), NAND (2 to 16 inputs),
latch (reset-dominant), edge detectors, timers
any logical variable, contact, or virtual input
32
0 to 60000 (ms, sec., min.) in steps of 1
0 to 60000 (ms, sec., min.) in steps of 1
4 (A through D)
40 (0 through 1 of pickup)
80 (1 through 20 of pickup)
0 to 65535 ms in steps of 1
up to 256 logical variables grouped under 16 Modbus addresses
any logical variable, contact, or virtual input
16
any analog actual value, or two values in differential mode
signed or absolute value
level, delta
over, under
–90.000 to 90.000 pu in steps of 0.001
0.1 to 50.0% in steps of 0.1
20 ms to 60 days
0.000 to 65.535 s in steps of 0.001
set-dominant or reset-dominant
16 (individually programmed)
stored in non-volatile memory
as input prior to protection, control, and FlexLogic
48 plus trip and alarm
from any logical variable, contact, or virtual input
self-reset or latched
from any contact input or user-programmable condition
3, interruptible at any time
approximately 3 minutes
all LEDs on
all LEDs off, one LED at a time on for 1 s
all LEDs on, one LED at a time off for 1 s
16
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
CHAPTER 2: PRODUCT DESCRIPTION