CHAPTER 5: SETTINGS
simplified by placing an "END" operator within the overall set of FlexLogic equations. The equations are evaluated up
to the first "END" operator.
The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.

5.6.5 FlexLogic equation editor

SETTINGS  FLEXLOGIC  FLEXLOGIC EQUATION EDITOR
 FLEXLOGIC
 EQUATION EDITOR
There are 512 FlexLogic entries available, numbered from 1 to 512, with default END entry settings. If a "Disabled" element
is selected as a FlexLogic entry, the associated state flag is never set to '1'. Press the +/– key when editing FlexLogic
equations to quickly scan through the major parameter types.

5.6.6 FlexLogic timers

SETTINGS  FLEXLOGIC  FLEXLOGIC TIMERS  FLEXLOGIC TIMER 1(32)
 FLEXLOGIC
 TIMER 1
There are 32 identical FlexLogic timers available. These timers are used as operators for FlexLogic equations.
— Selects the time measurement unit.
TIMER 1 TYPE
— Sets the time delay to pickup. If a pickup delay is not required, set this function to "0."
TIMER 1 PICKUP DELAY
— Sets the time delay to dropout. If a dropout delay is not required, set this function to "0."
TIMER 1 DROPOUT DELAY

5.6.7 FlexElements

SETTINGS  FLEXLOGIC  FLEXELEMENTS  FLEXELEMENT 1(16)
 FLEXELEMENT 1
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
FLEXLOGIC ENTRY 1:
END
FLEXLOGIC ENTRY 512:
END
TIMER 1
TYPE: millisecond
TIMER 1 PICKUP
DELAY:
0
TIMER 1 DROPOUT
DELAY:
0
FLEXELEMENT 1
FUNCTION: Disabled
FLEXELEMENT 1 NAME:
FxE 1
FLEXELEMENT 1 +IN:
Off
FLEXELEMENT 1 -IN:
Off
FLEXELEMENT 1 INPUT
MODE: SIGNED
FLEXELEMENT 1 COMP
MODE: LEVEL
FLEXELEMENT 1
DIRECTION: OVER
Range: FlexLogic operands
Range: FlexLogic operands
Range: millisecond, second, minute
Range: 0 to 60000 in steps of 1
Range: 0 to 60000 in steps of 1
Range: Disabled, Enabled
Range: up to six alphanumeric characters
Range: Off, any analog actual value parameter
Range: Off, any analog actual value parameter
Range: SIGNED, ABSOLUTE
Range: LEVEL, DELTA
Range: OVER, UNDER
FLEXLOGIC
5