GE C70 Instruction Manual page 268

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

FLEXLOGIC
Operand type
SELF-DIAGNOSTICS
(See Relay Self-tests
descriptions in
Chapter 7:
Commands and
Targets)
TEMPERATURE
MONITOR
USER-
PROGRAMMABLE
PUSHBUTTONS
5
Some operands can be re-named. These are the names of the breakers in the breaker control feature, the ID (identification)
of contact inputs, the ID of virtual inputs, and the ID of virtual outputs. If the user changes the default name or ID of any of
these operands, the assigned name appears in the relay list of operands. The default names are shown in the FlexLogic
operands table.
The characteristics of the logic gates are tabulated in the following table, and the operators available in FlexLogic are
listed in the FlexLogic operators table.
Table 5-18: FlexLogic gate characteristics
Gates
NOT
OR
AND
NOR
NAND
XOR
5-144
Operand syntax
ANY MAJOR ERROR
ANY MINOR ERROR
ANY SELF-TESTS
BATTERY FAIL
CLOCK UNSYNCHRONIZED
DIRECT DEVICE OFF
DIRECT RING BREAK
EQUIPMENT MISMATCH
FLEXLOGIC ERR TOKEN
LATCHING OUT ERROR
MAINTENANCE ALERT
FIRST ETHERNET FAIL
PROCESS BUS FAILURE
PTP FAILURE
RxGOOSE OFF
RRTD COMM FAIL
SECOND ETHERNET FAIL
THIRD ETHERNET FAIL
SNTP FAILURE
SYSTEM EXCEPTION
TEMP MONITOR
UNIT NOT PROGRAMMED
TEMP MONITOR
PUSHBUTTON 1 ON
PUSHBUTTON 1 OFF
ANY PB ON
PUSHBUTTON 2 to 12
Number of inputs
Output is '1' (= ON) if...
1
input is '0'
2 to 16
any input is '1'
2 to 16
all inputs are '1'
2 to 16
all inputs are '0'
2 to 16
any input is '0'
2
only one input is '1'
Operand description
Any of the major self-test errors generated (major error)
Any of the minor self-test errors generated (minor error)
Any self-test errors generated (generic, any error)
The battery is not functioning. Replace as outlined in the Maintenance
chapter.
Relay is not synchronized to the international time standard
A direct device is configured but not connected
The Direct I/O settings is for a connection that is not in a ring
The configuration of modules does not match the stored order code
A FlexLogic equation is incorrect
A difference is detected between the desired and actual latch contact state
A subset of the minor self-test errors generated, see Chapter 7
Link failure detected. See description in Chapter 7: Commands and Targets.
See description in Chapter 7: Commands and Targets
"Bad PTP Signal" self-test as described in Chapter 7
One or more GOOSE messages are not being received
See description in Chapter 7: Commands and Targets
See description in Chapter 7: Commands and Targets
See description in Chapter 7: Commands and Targets
SNTP server is not responding
See description in Chapter 7: Commands and Targets
Monitors ambient temperature and maximum operating temperature
The product SETUP > INSTALLATION > RELAYS SETTINGS setting is not
programmed
Asserted while the ambient temperature is greater than the maximum
operating temperature (80°C)
Pushbutton number 1 is in the "On" position
Pushbutton number 1 is in the "Off" position
Any of 12 pushbuttons is in the "On" position
Same set of operands as PUSHBUTTON 1
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL