CHAPTER 8: APPLICATION OF SETTINGS
The following figure illustrates parallel capacitor banks, ungrounded, no tap available, and with current unbalance
protection. In this case, two CT/VT modules are required.
Figure 8-8: Parallel banks, ungrounded, no tap available, current unbalance protection
The following figure illustrates parallel capacitor banks, grounded, no tap available, and with current unbalance protection.
In this case, two CT/VT modules are required.
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Figure 8-7: Single bank, grounded, with a tap
PROTECTION METHODS FOR CAPACITOR BANKS
C70 CAPACITOR BANK RELAY
50P
51P
51N
87V
59B
834759A1.CDR
C70 CAPACITOR BANK RELAY
50P
51P
60P
(C)
59B
59NU
60P
(B)
60P
(A)
51N
60N
834760A1.CDR
8-7