ENERVISTA SOFTWARE INTERFACE
2.
Enter the serial number of the C70 device to lock to the settings file in the Serial # Lock field.
3.
Click the OK button to apply the change.
4
The settings file and corresponding secure FlexLogic equations are now locked to the C70 device specified by the serial
number.

4.1.8 Settings file traceability

A traceability feature for settings files allows the user to quickly determine if the settings in a C70 device have been
changed since the time of installation from a settings file. When a settings file is transferred to a C70 device, the date, time,
and serial number of the C70 are sent back to EnerVista UR Setup and added to the settings file on the local computer. This
information can be compared with the C70 actual values at any later date to determine if security has been compromised.
The traceability information is only included in the settings file if a complete settings file is either transferred to the C70
device or obtained from the C70 device. Any partial settings transfers by way of drag and drop do not add the traceability
information to the settings file.
4-10
Figure 4-11: Settings file properties window
Figure 4-12: Settings file traceability
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL