GROUPED ELEMENTS
Multiplier
(TDM)
600.00
FlexCurves
FlexCurves are described in the FlexCurves section later in this chapter. The curve shapes for the FlexCurves are derived
from the formulae:
where
T = operate time (in seconds)
TDM = Multiplier setting
I = Input Current
I
= Pickup Current setting
pickup
T
= Reset Time in seconds (assuming energy capacity is 100% and
RESET
Definite time curve
The Definite Time curve shape operates as soon as the pickup level is exceeded for a specified period of time. The base
definite time curve delay is in seconds. The curve multiplier of 0.00 to 600.00 makes this delay adjustable from
5
instantaneous to 600.00 seconds in steps of 10 ms. The definite time curve shapes are defined as follows:
where
T = Operate Time (in seconds)
TDM = Multiplier setting
I = Input Current
I
= Pickup Current setting
pickup
T
= Reset Time in seconds (assuming energy capacity is 100% and RESET: Timed)
RESET
Recloser curves
The C70 uses the FlexCurve feature to facilitate programming of 41 recloser curves. See the FlexCurves settings section
earlier in this chapter for details.
5.7.3.3 Phase time overcurrent (ANSI 51P, IEC PTOC)
SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  PHASE CURRENT  PHASE TOC1(6)
 PHASE TOC 1
5-162
Current ( I / I
)
pickup
1.5
2.0
3.0
26666.7
15000.0
6666.7
T
=
TDM
×
FlexCurve Time at
×
T
=
TDM
FlexCurve Time at
RESET
T
=
TDM in seconds, when I I
T
RESET
PHASE TOC1
FUNCTION: Disabled
PHASE TOC1 SIGNAL
SOURCE: SRC 1
PHASE TOC1
INPUT: Phasor
PHASE TOC1
PICKUP: 1.000 pu
4.0
5.0
6.0
3750.0
2400.0
1666.7
I
I
------------- -
------------- -
when
I
I
pickup
pickup
I
------------- -
------------- -
when
I
I
pickup
pickup
: Timed)
RESET
>
pickup
=
TDM in seconds
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: Phasor, RMS
Range: 0.000 to 30.000 pu in steps of 0.001
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
7.0
8.0
9.0
1224.5
937.50
740.74
1.00
I
0.98
10.0
600.00
Eq. 5-11
Eq. 5-12
Eq. 5-13
Eq. 5-14