GE C70 Instruction Manual page 260

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

FLEXLOGIC
Operand type
ELEMENT:
Breaker control
5
ELEMENT:
Capacitor control
ELEMENT:
Digital counters
5-136
Operand syntax
BREAKER 1 OFF CMD
BREAKER 1 ON CMD
BREAKER 1 ΦA BAD ST
BREAKER 1 ΦA INTERM
BREAKER 1 ΦA CLSD
BREAKER 1 ΦA OPEN
BREAKER 1 ΦB BAD ST
BREAKER 1 ΦB INTERM
BREAKER 1 ΦB CLSD
BREAKER 1 ΦB OPEN
BREAKER 1 ΦC BAD ST
BREAKER 1 ΦC INTERM
BREAKER 1 ΦC CLSD
BREAKER 1 ΦC OPEN
BREAKER 1 BAD STATUS
BREAKER 1 CLOSED
BREAKER 1 OPEN
BREAKER 1 DISCREP
BREAKER 1 TROUBLE
BREAKER 1 MNL CLS
BREAKER 1 TRIP A
BREAKER 1 TRIP B
BREAKER 1 TRIP C
BREAKER 1 ANY P OPEN
BREAKER 1 ONE P OPEN
BREAKER 1 OOS
BREAKER 2 to 6
CAP 1 IN REMOTE
CAP 1 IN LOCAL
CAP 1 IN AUTO
CAP 1 IN MAN
CAP 1 DISCHARGING
CAP 1 BKR TRIP
CAP 1 BKR CLOSE
CAP 2 to 4
Counter 1 HI
Counter 1 EQL
Counter 1 LO
Counter 2 to 8
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
Operand description
Breaker 1 open command initiated
Breaker 1 close command initiated
Breaker 1 phase A bad status is detected (discrepancy between the 52/a and
52/b contacts)
Breaker 1 phase A intermediate status is detected (transition from one
position to another)
Breaker 1 phase A is closed
Breaker 1 phase A is open
Breaker 1 phase B bad status is detected (discrepancy between the 52/a and
52/b contacts)
Breaker 1 phase B intermediate status is detected (transition from one
position to another)
Breaker 1 phase B is closed
Breaker 1 phase B is open
Breaker 1 phase C bad status is detected (discrepancy between the 52/a and
52/b contacts)
Breaker 1 phase C intermediate status is detected (transition from one
position to another)
Breaker 1 phase C is closed
Breaker 1 phase C is open
Breaker 1 bad status is detected on any pole
Breaker 1 is closed
Breaker 1 is open
Breaker 1 has discrepancy
Breaker 1 trouble alarm
Breaker 1 manual close
Breaker 1 trip phase A command
Breaker 1 trip phase B command
Breaker 1 trip phase C command
At least one pole of breaker 1 is open
Only one pole of breaker 1 is open
Breaker 1 is out of service
Same set of operands as shown for BREAKER 1
Capacitor control element 1 in remote control mode
Capacitor control element 1 in local control mode
Capacitor control element 1 in automatic mode
Capacitor control element 1 in manual mode
Capacitor 1 is discharging; asserted till discharge delay expires
Capacitor 1 breaker trip command
Capacitor 1 breaker close command
Same set of operands as shown for CAP 1
Digital counter 1 output is 'more than' comparison value
Digital counter 1 output is 'equal to' comparison value
Digital counter 1 output is 'less than' comparison value
Same set of operands as shown for Counter 1