CHAPTER 5: SETTINGS
When entering a settings or command password via EnerVista or any serial interface, the user must enter the
corresponding connection password. If the connection is to the back of the C70, the remote password must be used. If the
connection is to the RS232 port of the faceplate, the local password must be used.
The local setting and command sessions are initiated by the user through the front panel display and are disabled either by
the user or by timeout (via the setting and command level access timeout settings). The remote setting and command
sessions are initiated by the user through the EnerVista software and are disabled either by the user or by timeout.
The state of the session (local or remote, setting or command) determines the state of the following FlexLogic operands:
— Asserted when local setting access is disabled
ACCESS LOC SETG OFF
— Asserted when local setting access is enabled
ACCESS LOC SETG ON
— Asserted when local command access is disabled
ACCESS LOC CMND OFF
— Asserted when local command access is enabled
ACCESS LOC CMND ON
— Asserted when remote setting access is disabled
ACCESS REM SETG OFF
— Asserted when remote setting access is enabled
ACCESS REM SETG ON
— Asserted when remote command access is disabled
ACCESS REM CMND OFF
— Asserted when remote command access is enabled
ACCESS REM CMND ON
A command or setting write operation is required to update the state of the remote and local security
operands listed.
NOTE
— This setting allows recording of password access events in the event recorder.
PASSWORD ACCESS EVENTS
Change local passwords
SETTINGS  PRODUCT SETUP  SECURITY  CHANGE LOCAL PASSWORDS
 CHANGE LOCAL
 PASSWORDS
As outlined in the previous section, there are two user security access levels, setting and command. Use of a password for
each level controls whether users can enter commands or change settings.
Proper password codes are required to enable each access level. When a
setting is programmed to "Yes" via the front panel interface, the following message sequence is
SETTING PASSWORD
invoked:
1.
ENTER NEW PASSWORD: ____________.
2.
VERIFY NEW PASSWORD: ____________.
3.
NEW PASSWORD HAS BEEN STORED.
To gain write access to a "Restricted" setting, program the
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access is allowed. Access automatically reverts to the "Restricted" level according to the
access level timeout setting values and when power is cycled.
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
CHANGE COMMAND
PASSWORD: No
CHANGE SETTING
PASSWORD: No
ENCRYPTED COMMAND
PASSWORD: ----------
ENCRYPTED SETTING
PASSWORD: ----------
ACCESS LEVEL
Range: No, Yes
Range: No, Yes
Range: 0 to 9999999999
Note: ---------- indicates no password
Range: 0 to 9999999999
Note: ---------- indicates no password
CHANGE COMMAND PASSWORD
setting in the main security menu to "Setting" and
PRODUCT SETUP
5
or
CHANGE
5-9