GE C70 Instruction Manual page 212

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

PRODUCT SETUP
Table 5-11: Oscillography cycles/record example
Records
CT/VTs
3
1
3
1
8
1
8
1
8
2
8
2
8
2
8
2
32
2
— A new record automatically overwrites an older record when
TRIGGER MODE
Overwrite."
TRIGGER POSITION
position of 25% consists of 25% pre- and 75% post-trigger data.
— Always captured in oscillography and can be any FlexLogic parameter (element state, contact input,
TRIGGER SOURCE
virtual output, and so on). The relay sampling rate is 64 samples per cycle.
AC INPUT WAVEFORMS
Reducing the sampling rate allows longer records to be stored. This setting has no effect on the internal sampling rate of
the relay, which is always 64 samples per cycle. That is, it has no effect on the fundamental calculations of the device.
5
When changes are made to the oscillography settings, all existing oscillography records are cleared.
NOTE
5.3.8.2 Digital channels
SETTINGS  PRODUCT SETUP  OSCILLOGRAPHY  DIGITAL CHANNELS
 DIGITAL CHANNELS
DIGITAL 1(63) CHANNEL
each oscillography trace depends in part on the number of parameters selected here. Parameters set to "Off" are ignored.
5.3.8.3 Analog channels
SETTINGS  PRODUCT SETUP  OSCILLOGRAPHY  ANALOG CHANNELS
 ANALOG CHANNELS
These settings select the metering actual value recorded in an oscillography trace. The length of each oscillography trace
depends in part on the number of parameters selected here. Parameters set to "Off" are ignored. The parameters available
in a given relay depend on
the type of relay,
5-88
Sample rate
Digital
8
0
16
16
16
16
16
16
16
16
16
63
32
63
64
63
64
63
— Set this to a percentage of the total buffer size (for example, 10%, 50%, 75%, and so on). A trigger
— Determines the sampling rate at which AC input signals (that is, current and voltage) are stored.
DIGITAL CHANNEL 1:
Off
DIGITAL CHANNEL 63:
Off
— This setting selects the FlexLogic operand state recorded in an oscillography trace. The length of
ANALOG CHANNEL 1:
Off
ANALOG CHANNEL 16:
Off
Analog
0
0
0
4
4
16
16
16
16
Range: FlexLogic operand
Range: FlexLogic operand
Range: Off, any FlexAnalog parameter
See Appendix A for list
Range: Off, any FlexAnalog parameter
See Appendix A for list
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Cycles/
record
14663
6945
3472
2868
1691
1221
749
422
124
is set to "Automatic
TRIGGER MODE