Breaker Failure (Ansi 50Bf) - GE C70 Instruction Manual

Capacitor bank protection and control system
Hide thumbs Also See for C70:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS

5.7.7 Breaker failure (ANSI 50BF)

SETTINGS  GROUPED ELEMENTS  SETTING GROUP 1(6)  BREAKER FAILURE  BREAKER FAILURE 1
 BREAKER FAILURE 1
C70 CAPACITOR BANK PROTECTION AND CONTROL SYSTEM – INSTRUCTION MANUAL
BF1 FUNCTION:
Disabled
BF1 MODE:
3-Pole
BF1 SOURCE:
SRC 1
BF1 USE AMP SUPV:
Yes
BF1 USE SEAL-IN:
Yes
BF1 3-POLE INITIATE:
Off
BF1 BLOCK:
Off
BF1 PH AMP SUPV
PICKUP: 1.050 pu
BF1 N AMP SUPV
PICKUP: 1.050 pu
BF1 USE TIMER 1:
Yes
BF1 TIMER 1 PICKUP
DELAY: 0.000 s
BF1 USE TIMER 2:
Yes
BF1 TIMER 2 PICKUP
DELAY: 0.000 s
BF1 USE TIMER 3:
Yes
BF1 TIMER 3 PICKUP
DELAY: 0.000 s
φ
BF1 BKR POS1
A/3P:
Off
φ
BF1 BKR POS2
A/3P:
Off
BF1 BREAKER TEST ON:
Off
BF1 PH AMP HISET
PICKUP: 1.050 pu
BF1 N AMP HISET
PICKUP: 1.050 pu
BF1 PH AMP LOSET
PICKUP: 1.050 pu
BF1 N AMP LOSET
PICKUP: 1.050 pu
BF1 LOSET TIME
DELAY: 0.000 s
GROUPED ELEMENTS
Range: Disabled, Enabled
Range: 3-Pole, 1-Pole
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: Yes, No
Range: Yes, No
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: Yes, No
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.001 to 30.000 pu in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
5
5-191

Advertisement

Table of Contents
loading

Table of Contents