Configuration Parameters; Settings Parameters - GE PACSystems RX7i Reference Manual

Cpu
Hide thumbs Also See for PACSystems RX7i:
Table of Contents

Advertisement

3.2

Configuration Parameters

3.2.1 Settings Parameters

These parameters specify basic operating characteristics of the CPU. For details on how these
parameters affect CPU operation, refer to PACSystems RX7i, RX3i and RSTi-EP CPU Programmer's
Reference Manual, GFK-2950 Chapter 2.
Settings Parameters
Passwords
Specifies whether passwords are Enabled or Disabled. Default: Enabled.
Note:
When passwords are disabled, they cannot be re-enabled without clearing PLC memory.
Stop-Mode I/O
Specifies whether the I/O is scanned while the PLC is in STOP Mode. Default: Disabled.
Scanning
(Always Disabled for Redundancy CPU.)
Note:
Watchdog
(Denominated in ms, set in 10ms increments.) Requires a value that is greater than the
Timer (ms)
program sweep time.
The software watchdog timer is designed to detect failure to complete sweep conditions.
The CPU restarts the watchdog timer at the beginning of each sweep. The watchdog timer
accumulates time during the sweep. The software watchdog timer is useful in detecting
abnormal operation of the application program, which could prevent the PLC sweep from
completing within the watchdog time period.
Valid range: 10 ms through 2550 ms, in increments of 10 ms.
Default: 200.
For details on setting the watchdog timer in a CPU redundancy system, refer to the
PACSystems Hot Standby CPU Redundancy User Manual, GFK-2308.
Logic/
Specifies the location/source of the logic and configuration data that is to be used (or
Configuration
loaded/copied into RAM) after each power up.
Power-up
Choices: Always RAM, Always Flash, Conditional Flash.
Source
Default: Always RAM.
Data Power-up
Specifies the location/source of the reference data that is to be used (or loaded/copied into
Source
RAM) after each power up.
Choices: Always RAM, Always Flash, Conditional Flash.
Default: Always RAM.
67
For availability, refer to the Important Product Information document for the CPU firmware version that you are using.
GFK-2222AD
67
If Enhanced Security
is enabled in the target properties, the Passwords setting
will be Enabled and read-only, and the Access Control tab appears.
This parameter corresponds to the I/O ScanStop parameter on a Series 90-70 PLC.
April 2018
Chapter 3. CPU Configuration
111

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pacsystems rsti-epPacsystems rx3i

Table of Contents