7 How to Program the Adjustable Frequency
Drive

0-20 Display Line 1.1 Small

Option:
[0]
None
[37]
Display Text 1
[38]
Display Text 2
[39]
Display Text 3
[89]
Date and Time Readout
[953]
Profibus Warning Word
[1005]
Readout Transmit Error Counter
[1006]
Readout Receive Error Counter
[1007]
Readout Bus Off Counter
7
[1013]
Warning Parameter
[1115]
LON Warning Word
[1117]
XIF Revision
[1118]
LonWorks Revision
[1501]
Running Hours
[1502]
kWh Counter
[1600]
Control Word
[1601]
Reference [Unit]
[1602] *
Reference %
[1603]
Status Word
[1605]
Main Actual Value [%]
[1609]
Custom Readout
[1610]
Power [kW]
[1611]
Power [hp]
[1612]
Motor voltage
[1613]
Frequency
[1614]
Motor Current
[1615]
Frequency [%]
[1616]
Torque [Nm]
7-8
Function:
Select a variable for display in line 1, left position.
No display value selected
Enables an individual text string to be written, for display in the LCP or to be read via serial com-
munication.
Enables an individual text string to be written, for display in the LCP or to be read via serial com-
munication.
Enables an individual text string to be written, for display in the LCP or to be read via serial com-
munication.
Displays the current date and time.
Displays Profibus communication warnings.
View the number of CAN control transmission errors since the last power-up.
View the number of CAN control receipt errors since the last power-up.
View the number of Bus Off events since the last power-up.
View a DeviceNet-specific warning word. One separate bit is assigned to every warning.
Shows the LON-specific warnings.
Shows the version of the external interface file of the Neuron C chip on the LON option.
Shows the software version of the application program of the Neuron C chip on the LON option.
View the number of running hours of the motor.
View the line power consumption in kWh.
View the control word sent from the adjustable frequency drive via the serial communication port
in hex code.
Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and slow-down) in selected
unit.
Total reference (sum of digital/analog/preset/bus/freeze ref./catch up and slow-down) in percent.
Present status word
View the two-byte word sent with the status word to the bus master reporting the main actual value.
View the user-defined readouts as defined in par. 0-30
Readout Min Value
Custom Readout Max Value
and par. 0-32
Actual power consumed by the motor in kW.
Actual power consumed by the motor in HP.
Voltage supplied to the motor.
Motor frequency, i.e., the output frequency from the adjustable frequency drive in Hz.
Phase current of the motor measured as effective value.
Motor frequency, i.e., the output frequency from the adjustable frequency drive in percent.
Present motor load as a percentage of the rated motor torque.
MG.11.AB.22 - VLT
®
is a registered Danfoss trademark
VLT
®
HVAC Drive Instruction Manual
Custom Readout Unit
, par. 0-31
Custom
.