Short Cycle Protection; Flow Compensation; Square-Linear Curve Approximation - Danfoss VLT HVACDrive Instruction Manual

Table of Contents

Advertisement

7 How to Program the Adjustable Frequency
Drive

22-75 Short Cycle Protection

Option:
[0] *
Disabled
[1]
Enabled
22-76 Interval between Starts
Range:
Application
[Application dependant]
dependent*
22-77 Minimum Run Time
Range:
0 s*
[Application dependant]
7
NOTE!
Does not work in cascade mode.

22-80 Flow Compensation

Option:
[0] *
Disabled
[1]
Enabled

22-81 Square-linear Curve Approximation

Range:
100 %*
[0 - 100 %]
NOTE!
Please note: Not visible when running in cascade.
7-46
Function:
Timer set in par. 22-76
Interval between Starts
Timer set in par. 22-76
Interval between Starts
Function:
Function:
Sets the time desired as minimum run time after a normal start command (Start/Jog/Freeze). Any
normal stop command will be disregarded until the set time has expired. The timer will start counting
following a normal start command (Start/Jog/Freeze).
The timer will be overridden by a Coast (Inverse) or an External Interlock command.
Function:
Disabled
[0]
: Setpoint compensation not active.
Enabled
[1]
: Setpoint compensation is active. Enabling this parameter allows the Flow Compensated
Setpoint operation.
Function:
Example 1:
Adjustment of this parameter allows the shape of the control curve to be adjusted.
0 = Linear
100% = Ideal shape (theoretical).
MG.11.AB.22 - VLT
®
is a registered Danfoss trademark
VLT
®
HVAC Drive Instruction Manual
is disabled.
is enabled.