4 Electrical Installation

4.1.14 Motor Connection for A2 and A3

Follow these drawings step-by-step for connecting the motor to the adjustable frequency drive.
4
Figure 4.18: First terminate the motor ground, then place motor U, V and W wires in the plug and tighten them.
Figure 4.19: Mount cable clamp to ensure 360 degree connection between chassis and shield; ensure that the outer insulation of the motor
cable is removed under the clamp.
4-18