Ul Compliance Fuses - Danfoss VLT HVACDrive Instruction Manual

Table of Contents

Advertisement

4 Electrical Installation
If UL/cUL is not to be complied with, we recommend using the following fuses, which will ensure compliance with EN50178:
Adjustable Frequency Drive
P110 - P250
P315 - P450
Table 4.4: Compliance with EN50178

UL compliance fuses

4
Adjustable
frequency
Bussmann
drive
200–240 V
kW
Type RK1
K25-K37
KTN-R05
K55-1K1
KTN-R10
1K5
KTN-R15
2K2
KTN-R20
3K0
KTN-R25
3K7
KTN-R30
5K5
KTN-R50
7K5
KTN-R50
11K
KTN-R60
15K
KTN-R80
18K5
KTN-R125
22K
KTN-R125
30K
FWX-150
37K
FWX-200
45K
FWX-250
Table 4.5: UL fuses, 200–240 V
4-6
Voltage
380–480 V
380–480 V
Bussmann
Bussmann
Type J
Type T
JKS-05
JJN-05
JKS-10
JJN-10
JKS-15
JJN-15
JKS-20
JJN-20
JKS-25
JJN-25
JKS-30
JJN-30
JKS-50
JJN-50
JKS-60
JJN-60
JKS-60
JJN-60
JKS-80
JJN-80
JKS-150
JJN-125
JKS-150
JJN-125
-
-
-
-
-
-
MG.11.AB.22 - VLT
VLT
SIBA
Littel fuse
Type RK1
Type RK1
5017906-005
KLN-R005
5017906-010
KLN-R10
5017906-015
KLN-R15
5012406-020
KLN-R20
5012406-025
KLN-R25
5012406-030
KLN-R30
5012406-050
KLN-R50
5012406-050
KLN-R60
5014006-063
KLN-R60
5014006-080
KLN-R80
2028220-125
KLN-R125
2028220-125
KLN-R125
2028220-150
L25S-150
2028220-200
L25S-200
2028220-250
L25S-250
®
is a registered Danfoss trademark
®
HVAC Drive Instruction Manual
Type
type gG
type gR
Ferraz-
Ferraz-
Shawmut
Shawmut
Type CC
Type RK1
ATM-R05
A2K-05R
ATM-R10
A2K-10R
ATM-R15
A2K-15R
ATM-R20
A2K-20R
ATM-R25
A2K-25R
ATM-R30
A2K-30R
-
A2K-50R
-
A2K-50R
A2K-60R
A2K-60R
A2K-80R
A2K-80R
A2K-125R
A2K-125R
A2K-125R
A2K-125R
A25X-150
A25X-150
A25X-200
A25X-200
A25X-250
A25X-250

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt hvac drive fc 100 series

Table of Contents