6-51 Terminal 42 Output Min Scale

Range:
0.00 %*
[0.00 - 200.00 %]

6-52 Terminal 42 Output Max Scale

Range:
100.00 %*
[0.00 - 200.00 %]
EXAMPLE 1:
Variable value= OUTPUT FREQUENCY, range = 0–100 Hz
Range needed for output = 0–50 Hz
Output signal 0 or 4 mA is needed at 0 Hz (0% of range) - set par. 6-51
Output signal 20 mA is needed at 50 Hz (50% of range) - set par. 6-52
EXAMPLE 2:
Variable= FEEDBACK, range= -200% to +200%
Range needed for output= 0–100%
Output signal 0 or 4 mA is needed at 0% (50% of range) - set par. 6-51
Output signal 20 mA is needed at 100% (75% of range) - set par. 6-52