Fuses; Branch Circuit Protection - Danfoss VLT HVACDrive Instruction Manual

Table of Contents

Advertisement

4 Electrical Installation
Terminal number
1+2+3
4+5+6
12
13
18
19
20
27
29
32
4
33
37
42
53
54
Table 4.2: Terminal connections
Very long control cables and analog signals may, in rare cases and depending on the installation, result in 50/60 Hz ground loops due to noise from line
power supply cables.
If this occurs, break the shield or insert a 100 nF capacitor between shield and chassis.
NOTE!
The common of digital / analog inputs and outputs should be connected to separate common terminals 20, 39, and 55. This will prevent
ground current interference among groups. For example, it prevents switching on digital inputs from disturbing analog inputs.
NOTE!
To comply with EMC emission specifications, shielded/armored cables are recommended. If an unshielded/unarmored cable is used,
see section

4.1.4 Fuses

Branch Circuit Protection

In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines, etc., must be short-circuit
and overcurrent protected according to the national/international regulations.
Short-circuit protection:
The adjustable frequency drive must be protected against short-circuit to avoid electrical or fire hazard. Danfoss recommends using
the fuses mentioned below to protect service personnel and equipment in case of an internal failure in the drive. The adjustable
frequency drive provides full short-circuit protection in case of a short-circuit on the motor output.
4-4
Terminal description
Terminal 1+2+3-Relay1
Terminal 4+5+6-Relay2
Terminal 12 Supply
Terminal 13 Supply
Terminal 18 Digital Input
Terminal 19 Digital Input
Terminal 20
Terminal 27 Digital Input/Output
Terminal 29 Digital Input/Output
Terminal 32 Digital Input
Terminal 33 Digital Input
Terminal 37 Digital Input
Terminal 42 Analog Output
Terminal 53 Analog Input
Terminal 54 Analog Input
Power and Control Wiring for Unshielded Cables
MG.11.AB.22 - VLT
VLT
®
Parameter number
5-40
5-40
-
-
5-10
5-11
-
5-12/5-30
5-13/5-31
5-14
5-15
-
6-50
3-15/6-1*/20-0*
3-15/6-2*/20-0*
.. For more information, see
EMC Test Results
®
is a registered Danfoss trademark
HVAC Drive Instruction Manual
Factory default
No operation
No operation
+24 V DC
+24 V DC
Start
No operation
Common
Coast inverse
Jog
No operation
No operation
Safe Stop
Speed 0-HighLim
Reference
Feedback
in the Design Guide.