Setpoints - Danfoss VLT HVACDrive Instruction Manual

Table of Contents

Advertisement

VLT
®
HVAC Drive Instruction Manual
Example 2: Multi-zone, multi setpoint
The previous example can be used to illustrate the use of multi-zone, multi-setpoint control. If the zones require different pressures for each VAV box,
each setpoint may be specified in par. 20-21
Feedback Function
par. 20-20
, the PID controller will increase the speed of the fan if any one of the feedbacks is below its setpoint and decrease the
speed of the fan if all feedbacks are above their individual setpoints.
20-21 Setpoint 1
Range:
0.000 Proc-
[-999999.999 - 999999.999 Proc-
essCtrlU-
essCtrlUnit]
nit*
20-22 Setpoint 2
Range:
0.000 Proc-
[-999999.999 - 999999.999 Proc-
essCtrlU-
essCtrlUnit]
nit*
NOTE!
The setpoint reference entered here is added to any other references that are enabled (see par. group 3-1*).
Setpoint 1
, par. 20-22
Setpoint 2
and par. 20-23
Function:
Setpoint 1 is used in closed-loop mode to enter a setpoint reference that is used by the adjustable
frequency drive's PID controller. See the description of par. 20-20
NOTE!
Setpoint reference entered here is added to any other references that are enabled
(see par. group 3-1*).
Function:
Setpoint 2 is used in closed-loop mode to enter a setpoint reference that may be used by the ad-
justable frequency drive's PID controller. See the description of
Feedback Function
par. 20-20
.
MG.11.AB.22 - VLT
®
is a registered Danfoss trademark
7 How to Program the Adjustable Frequency
Setpoint 3
. By selecting
Multi-setpoint minimum
Feedback Function
Drive
, [5], in
7
.
Feedback Function
,
7-39

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt hvac drive fc 100 series

Table of Contents