7 How to Program the Adjustable Frequency
Drive

6-50 Terminal 42 Output

Option:
[0] *
No operation
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Feedback +-200%
[103]
Motor cur. 0-Imax
[104]
Torque 0-Tlim
[105]
Torque 0-Tnom
[106]
Power 0-Pnom
[107] *
Speed 0-HighLim
[113]
Ext. Closed-loop 1
7
[114]
Ext. Closed-loop 2
[115]
Ext. Closed-loop 3
[130]
Out fr 0-100 4-20
[131]
Reference 4-20mA
[132]
Feedback 4-20mA
[133]
Motor cur. 4-20mA
[134]
Torq.0-lim 4-20mA
[135]
Torq.0-nom 4-20mA
[136]
Power 4-20mA
[137]
Speed 4-20mA
[139]
Bus ctrl.
[140]
Bus ctrl. 4-20 mA
[141]
Bus ctrl t.o.
[142]
Bus ctrl 4-20mA t.o.
[143]
Ext. CL 1 4-20 mA
[144]
Ext. CL 2 4-20 mA
[145]
Ext. CL 3 4-20 mA
NOTE!
Values for setting the minimum reference are found in open-loop par. 3-02
Feedb.
- values for maximum reference for open-loop are found in par. 3-03
Feedb.
.
7-30
Function:
Select the function of Terminal 42 as an analog current output. A motor current of 20 mA corre-
sponds to I
.
max
: 0–100 Hz, (0–20 mA)
: Minimum reference - Maximum reference, (0–20 mA)
: -200% to +200% of par. 20-14
Maximum Reference/Feedb.
: 0 - Inverter Max. Current (par. 16-37
Torque Limit Motor Mode
: 0 - Torque limit (par. 4-16
: 0 - Motor rated torque, (0–20 mA)
: 0 - Motor rated power, (0–20 mA)
Motor Speed High Limit [RPM]
: 0 - Speed High Limit (par. 4-13
Limit [Hz]
), (0–20 mA)
: 0–100%, (0–20 mA)
: 0–100%, (0–20 mA)
: 0–100%, (0–20 mA)
: 0–100 Hz
: Minimum Reference - Maximum Reference
Maximum Reference/Feedb.
: -200% to +200% of par. 20-14
: 0 - Inverter Max. Current (par. 16-37
Torque Limit Motor Mode
: 0 - Torque limit (par. 4-16
: 0 - Motor rated torque
: 0 - Motor rated power
: 0 - Speed High Limit (4-13 and 4-14)
: 0–100%, (0–20 mA)
: 0 - 100%
: 0–100%, (0–20 mA)
: 0 - 100%
: 0 - 100%
: 0 - 100%
: 0 - 100%
Minimum Reference
Maximum Reference
MG.11.AB.22 - VLT
®
is a registered Danfoss trademark
VLT
®
HVAC Drive Instruction Manual
, (0–20 mA)
Inv. Max. Current
), (0–20 mA)
), (0–20 mA)
and par. 4-14
Inv. Max. Current
)
)
and for closed-loop par. 20-13
and for closed-loop par. 20-14
Motor Speed High
Minimum Reference/
Maximum Reference/