7 How to Program the Adjustable Frequency
Drive
[6]
Multi Setpoint Max
7
NOTE!
Any unused feedback must be set to "No function" in its Feedback Source parameter: Par. 20-00
par. 20-03
The feedback resulting from the function selected in par. 20-20
the adjustable frequency drive. This feedback can also be shown on the adjustable frequency drive's display, be used to control an adjustable frequency
drive's analog output, and be transmitted over various serial communication protocols.
The adjustable frequency drive can be configured to handle multi-zone applications. Two different multi-zone applications are supported:
Multi-zone, single setpoint
Multi-zone, multi setpoint
The difference between the two is illustrated by the following examples:
Example 1: Multi-zone, single setpoint
In an office building, a VAV (variable air volume) VLT HVAC Drive system must ensure a minimum pressure at selected VAV boxes. Due to the varying
pressure losses in each duct, the pressure at each VAV box cannot be assumed to be the same. The minimum pressure required is the same for all VAV
boxes. This control method can be set up by setting par. 20-20
Setpoint 1
par. 20-21
. The PID controller will increase the speed of the fan if any one feedback is below the setpoint, and decrease the speed of the fan
if all feedbacks are above the setpoint.
7-38
If all feedback signals are above their corresponding setpoints, the PID Controller will use the feed-
back/setpoint pair in which the difference between the feedback and setpoint is the least.
Multi-setpoint maximum
1 and Setpoint 1, Feedback 2 and Setpoint 2, and Feedback 3 and Setpoint 3. It will use the feed-
back/setpoint pair in which the feedback is farthest above its corresponding setpoint reference. If
all feedback signals are below their corresponding setpoints, the PID Controller will use the feed-
back/setpoint pair in which the difference between the feedback and the setpoint reference is the
least.
Feedback 2 Source
or par. 20-06
Feedback 3 Source
Feedback Function
MG.11.AB.22 - VLT
NOTE!
If only two feedback signals are used, the feedback that is not to be used must
be set to
No Function
in par. 20-00
Source
Feedback 3 Source
or par. 20-06
be the sum of its respective parameter value (par. 20-21
Setpoint 2
par. 20-22
and par. 20-23
are enabled (see par. group 3-1*).
[6] sets up the PID Controller to calculate the difference between Feedback
NOTE!
If only two feedback signals are used, the feedback that is not to be used must
No Function
be set to
in par. 20-00
Source
Feedback 3 Source
or par. 20-06
be the sum of its respective parameter value (par. 20-21
Setpoint 2
par. 20-22
and par. 20-23
are enabled (see par. group 3-1*).
.
will be used by the PID controller to control the output frequency of
Feedback Function
to option [3], Minimum, and entering the desired pressure in
®
is a registered Danfoss trademark
VLT
®
HVAC Drive Instruction Manual
Feedback 1 Source
, par. 20-03
Feedback 2
. Note that each setpoint reference will
Setpoint 1
Setpoint 3
) and any other references that
Feedback 1 Source
Feedback 2
, par. 20-03
. Note that each setpoint reference will
Setpoint 1
Setpoint 3
) and any other references that
Feedback 1 Source
,
,
,