Autoreclose - GE D60 Instruction Manual

Line distance protection system, ur series
Hide thumbs Also See for D60:
Table of Contents

Advertisement

5.7 CONTROL ELEMENTS

PATH: SETTINGS
CONTROL ELEMENTS
 AUTORECLOSE
5
5-264


AUTORECLOSE

AR FUNCTION:
Disabled
AR MODE:
MESSAGE
Mode 1 (1 & 3 Pole)
Mode 1 Activation:
MESSAGE
Off
Mode 2 Activation:
MESSAGE
Off
Mode 3 Activation:
MESSAGE
Off
Mode 4 Activation:
MESSAGE
Off
AR MAX NUMBER OF
MESSAGE
SHOTS: 2
AR INITIATE MODE:
MESSAGE
Protection AND CB
AR BLOCK BKR1:
MESSAGE
Off
AR CLOSE TIME BKR 1:
MESSAGE
0.10 s
AR BKR MAN CLOSE:
MESSAGE
Off
AR BLK TIME UPON MAN
MESSAGE
CLS:
10.00 s
AR 1P INIT:
MESSAGE
Off
AR 3P INIT:
MESSAGE
Off
AR 3P TD INIT:
MESSAGE
Off
AR MULTI-P FAULT:
MESSAGE
Off
BKR ONE POLE OPEN:
MESSAGE
Off
BKR 3 POLE OPEN:
MESSAGE
Off
AR 3-P DEAD TIME 1:
MESSAGE
0.50 s
AR 3-P DEAD TIME 2:
MESSAGE
1.20 s
AR 3-P DEAD TIME 3:
MESSAGE
2.00 s
D60 Line Distance Protection System
AUTORECLOSE
Range: Disabled, Enabled
Range: Mode 1(1 & 3 Pole), Mode 2 (1 Pole), Mode 3 (3
Pole-A), Mode 4 (3 Pole-B)
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 1, 2, 3, 4
Range: Protection AND CB, Protection Only
Range: FlexLogic operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
Range: 0.00 to 655.35 s in steps of 0.01
5 SETTINGS
5.7.10 AUTORECLOSE
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents