CHAPTER 5: SETTINGS
Table 5-14: Data logger storage capacity example
Sampling rate
Channels
15 ms
1
8
9
16
1000 ms
1
8
9
16
60000 ms
1
8
9
16
3600000 ms
1
8
9
Changing any setting affecting data logger operation clears data in the log.
— This setting configures the mode in which the data logger operates. When set to "Continuous," the
DATA LOGGER MODE
data logger actively records any configured channels at the rate as defined by the
idle in this mode when no channels are configured. When set to "Trigger," the data logger records any configured channels
at the instance of the rising edge of the
subsequent triggers and continues to record data until the active record is full. Once the data logger is full, a CLEAR DATA
LOGGER command is required to clear the data logger record before a new record can be started. Performing the CLEAR
DATA LOGGER command also stops the current record and resets the data logger to be ready for the next trigger.
— This setting selects the signal used to trigger the start of a new data logger record. Any FlexLogic
DATA LOGGER TRIGGER
operand can be used as the trigger source. This setting only applies when the mode is set to "Trigger."
— This setting selects the time interval at which the actual value data is recorded.
DATA LOGGER RATE
— This setting selects the metering actual value that is to be recorded in Channel 1(16) of the data
DATA LOGGER CHNL 1(16)
log. The parameters available in a given relay are dependent on: the type of relay, the type and number of CT/VT hardware
modules installed, and the type and number of Analog Input hardware modules installed. Upon startup, the relay
automatically prepares the parameter list. A list of all possible analog metering actual value parameters is shown in
Appendix A: FlexAnalog Parameters. The parameter index number shown in any of the tables is used to expedite the
selection of the parameter on the relay display. It can be time-consuming to scan through the list of parameters via the
relay keypad/display—entering this number via the relay keypad causes the corresponding parameter to display.
— This display presents the total amount of time that the Data Logger can record the channels not
DATA LOGGER CONFIG
selected to "Off" without overwriting old data.

5.3.11 User-programmable LEDs

5.3.11.1 Menu - Enhanced and standard front panels
SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE LEDS
 USER-PROGRAMMABLE
 LEDS
D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Days
Storage capacity
0.1
482 s
0.1
60 s
0.1
54 s
0.1
30 s
0.3
32729 s
0.1
4091 s
0.1
3637 s
0.1
2046 s
22.7
1963710 s
2.8
245460 s
2.5
218190 s
1.4
127230 s
1362.1
117822600 s
170.2
14727600 s
151.3
13091400 s
source FlexLogic operand. The data logger ignores all
DATA LOGGER TRIGGER
 LED TEST
. The data logger is
DATA LOGGER RATE
See below
PRODUCT SETUP
5
5-117