data logger will be idle in this mode if no channels are configured. When set to "Trigger", the data logger will begin to
record any configured channels at the instance of the rising edge of the
operand. The data logger will ignore all subsequent triggers and will continue to record data until the active record is
full. Once the data logger is full a
new record can be started. Performing the
the data logger to be ready for the next trigger.
DATA LOGGER TRIGGER: This setting selects the signal used to trigger the start of a new data logger record. Any
FlexLogic™ operand can be used as the trigger source. The
mode is set to "Trigger".
DATA LOGGER RATE: This setting selects the time interval at which the actual value data will be recorded.
DATA LOGGER CHNL 1(16): This setting selects the metering actual value that is to be recorded in Channel 1(16) of
the data log. The parameters available in a given relay are dependent on: the type of relay, the type and number of CT/
VT hardware modules installed, and the type and number of Analog Input hardware modules installed. Upon startup,
the relay will automatically prepare the parameter list. A list of all possible analog metering actual value parameters is
shown in Appendix A: FlexAnalog Parameters. The parameter index number shown in any of the tables is used to
expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the list of
parameters via the relay keypad/display – entering this number via the relay keypad will cause the corresponding
parameter to be displayed.
DATA LOGGER CONFIG: This display presents the total amount of time the Data Logger can record the channels not
selected to "Off" without over-writing old data.
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
 USER-PROGRAMMABLE
 LEDS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The 48 amber LEDs on relay panels 2 and 3 can be customized to illuminate when a selected FlexLogic™ operand is in the
logic 1 state. The trip and alarm LEDs on panel 1 can also be customized in a similar manner. To ensure correct functional-
ity of all LEDs, an LED test feature is also provided.
b) LED TEST
PATH: SETTINGS
PRODUCT SETUP
 LED TEST
MESSAGE
When enabled, the LED test can be initiated from any digital input or user-programmable condition such as user-program-
mable pushbutton. The control operand is configured under the
including the LEDs of the optional user-programmable pushbuttons.
GE Multilin
command is required to clear the data logger record before a
CLEAR DATA LOGGER
CLEAR DATA LOGGER


USER-PROGRAMMABLE LEDS

 LED TEST
 TRIP & ALARM LEDS
 USER-PROGRAMMABLE
 LED1
 USER-PROGRAMMABLE
 LED2
 USER-PROGRAMMABLE
 LED48

USER-PROGRAMMABLE LEDS
LED TEST FUNCTION:
Disabled
LED TEST CONTROL:
Off
D60 Line Distance Protection System
DATA LOGGER TRIGGER
command will also stop the current record and reset
setting only applies when the
DATA LOGGER TRIGGER
5.2.10 USER-PROGRAMMABLE LEDS
See below
See page 5–43.
See page 5–43.
LED TEST
Range: Disabled, Enabled.
Range: FlexLogic™ operand
setting. The test covers all LEDs,
LED TEST CONTROL
5.2 PRODUCT SETUP
source FlexLogic™
5
5-41