Setting the BACnet ID
This option is only available if the communication type ("Set Comm IF"
menu) for the device is BACnet and should only be configured by
qualified personnel. It allows users to program a specific MAC ID for the
device.
Scroll to the Set BACnet ID screen and press Enter to select.
Use the up or down buttons to increase or decrease the value to the
desired ID (between 0 and 4194303) and press Enter to confirm.
Note: The MAC ID must be unique. Selecting an ID that is already in use
may cause network conflicts.
The screen returns to the main menu option.
Setting the Baud Rate
This option let you select from a list of possible baud rates for the active
communication type.
Scroll to the Set Baud Rate screen and press Enter to select.
Use the up or down buttons to display the desired baud rate (available
rates are: 4800, 9600, 19200, 38400, 57600, 76800).
Note: The baud rate for a connection to a 301C is always 9600. The usual
baud rate is 9600 for BACnet communication.
* Menu *
Set BACNet ID
Set BACNet ID
1
* Menu *
Set Baud Rate.
Set Baud Rate
4800
IAQPoint User Manual
Using the IAQPoint
Programming Menus