Performing the firmware update
NOTICE
Note the following:
● With the next steps, all data on your CP are deleted and cannot be recovered!
● Do not cancel a download operation once it is started. The CP may no longer be usable
1. In the Siemens SIMATIC programs Start menu, select: STEP 7 > NCM S7 > Firmware
2. Click "Continue".
3. In the "Step 1" dialog box, set the path for the update file
4. Click "Next" to confirm the next three dialog boxes until you reach "Step 4: Perform Load
5. Read the information in the dialog box for "Step 4: Perform Load Operation".
6. Switch off the power supply of the rack.
7. Click "Cancel" to close the dialog box.
8. Reestablish the original PROFIBUS connection.
9. Switch on the power supply for the module.
States of the download operation
Where
On the PG/PC in the
Firmware Loader dialog box
On the PG/PC in the
Firmware Loader dialog box
CP 443-5 Extended
CP 443-5 Extended
Service support and diagnostics (V8.0)
Service Manual, 03/2012, A5E02779775-02
if you do this and you will have to send it in for repair.
Loader.
The dialog box of the firmware loader opens.
– Click the "Browse" button.
– Use "Select file" to select the desired file ("<drive>:\TEMP\Cp4435ex.fwl", for example).
– Click on the "Open" button.
Operation".
In the table below you will find the download operation states that are displayed.
The CP performs a self-test and is then ready for operation.
Display
The bar in the dialog box changes.
The message "Download completed
successfully" is displayed.
The CP RUN LED flashes.
The CP STOP LED is lit.
Ensuring Availability
3.3 Hardware update
State
Download procedure is running.
Download procedure is
complete.
Download procedure is running.
Download procedure is
complete.
47