5. Download this file to the CPU. The new CPU now has the same firmware version as the
6. Now connect the fiber-optic cable for the CPU of an H system.
You can then upgrade both CPUs of the H system to the latest firmware in the "Run" state.
Difference of the firmware update to a non-redundant system
Following the actual firmware update, a self-test starts automatically for the H-system. This
function may take several minutes. This time period depends on the amount of load memory
(size of the inserted memory card) and the amount of working memory.
Updating an H-CPU with an operating system update card
You can find additional information on this at the following Internet address:
http://www.automation.siemens.com/service
view/en/6741018)
3.3.4

Updating an interface module

3.3.4.1

Updating an interface module (IM)

Introduction
The interface modules (IM) ) are the interface to the PROFIBUS DP in PCS 7.
Preparation
● Compare the type and version of the interface modules you are using with the information
● If replacement of the interface module is required, contact your Siemens representative.
● A firmware update is possible for some interface modules. You will find the procedure in
Update capability of interface modules or couplers downstream from interface modules
You can update the firmware of the following components (interface modules or couplers
downstream from interface modules):
Components
IM 153-2
IM 152-1
Service support and diagnostics (V8.0)
Service Manual, 03/2012, A5E02779775-02
previously used CPU.
Switch the system to the "Redundant" operating mode by starting this CPU.
PCS 7 Released Modules.
in the document
the section "How to perform a firmware update of an IM (Page 40)" below.
Order Number
6ES7 153-2Bx00-0XB0
6ES7 152-1AA00-0AB0
(http://support.automation.siemens.com/WW/
As of firmware version
V2.02
Ensuring Availability
3.3 Hardware update