Siemens PCS 7 Service Manual page 108

Hide thumbs Also See for PCS 7:
Table of Contents

Advertisement

Diagnostics in PCS 7
7.18 Diagnostic tools
Thumbnail
active
standby
process mode
started at the server
Meaning of the thumbnail colors
The thumbnails can be visualized in the following colors:
● Thumbnail: Green
● Thumbnail: Magenta
● Thumbnail: Blue
● Thumbnail: Red
108
Meaning of the thumbnail
Readiness
The server is ready for operation, SIMATIC BATCH is not started
Status transition
A status transition is active at least at one server application.
Process mode is
The server application has assumed the process mode. This is the master in a
system with redundant servers.
Redundancy to
Only supported for redundant servers.
The server applications are prepared for process mode. The server is in standby
mode.
The server exits
Only supported for redundant servers.
The master exits process mode The server application is currently changing to
the standby mode.
Process mode is
Only supported for redundant servers.
The standby server assumes the master function. The server application is
currently changing to the master mode.
The thumbnail shows proper execution of the corresponding process.
Shows that the server application has logged on to the databases and to the process.
indicates an external fault (e.g. cable break at a network connection).
This is displayed after a fault state (error) was detected.
At least one of the SIMATIC BATCH components has reported an error.
Service support and diagnostics (V8.0)