Download  Print this page

Status Of Connections; Area Overview - Siemens PCS 7 Service Manual

Hide thumbs

Advertisement

7.18.4.7

Status of connections

Overview
Topic
Connection
status (OS-AS)
OS
connections
(server - client)
7.18.4.8

Area overview

Overview
Information on
Redundancy
status of the OS
server on the OS
client
Service support and diagnostics (V8.0)
Service Manual, 03/2012, A5E02779775-02
Detailed information
Connection between WinCC
and an automation system
Status - logical connections,
current status of the process
interface
Collective status of the
connection diagnostics of the
local client
Detailed information
Visual representation of the
redundancy monitoring
Green indicator:
● The monitored OS
servers are in process
mode and have the
status "OK".
Red indicator:
● Not all the monitored
servers are in process
mode.
● Not all the monitored
OS servers have the
status "OK".
● Not all the monitored
OS servers have a
correct network
connection.
No indicator:
● The process
"CCEmergencyWatchR
TServer.exe" is missing
in the startup list on the
OS client.
● No server data is loaded
on the OS client.
Called with
Additional information
Only when OS is in
Online help for
Information System , topic:
process mode: in the
menu of the WinCC
"Checking the status of the
Explorer. Options >
connection"
Status of Connections
See the section titled
"Status of multi-user
operation (Page 104)"
Called with
Additional information
Click the "Status of
Online help
Information System
the connected
server" icon in the
area overview in
process mode
Diagnostics in PCS 7
7.18 Diagnostic tools
WinCC
WinCC
105

Advertisement

   Also See for Siemens PCS 7

   Related Manuals for Siemens PCS 7

   Related Content for Siemens PCS 7

Comments to this Manuals

Symbols: 0
Latest comments: