Reset (RS)

This function resets an Inverter trip.
To reset an Inverter trip, press the STOP/RESET key on the Digital Operator, or turn ON the
reset (RS) terminal.
When using the reset terminal, allocate "18: RS" to a multi-function input terminal.
The restart method to be applied after the reset operation can be selected by Reset Restart
Selection (C103). Take note, however, that the Inverter will restart at 0 Hz if Reset Selection
(C102) is set to "03: Trip reset only," regardless of the setting of C103. If an overcurrent trip
occurs at frequency matching, extend the Restart Standby Time (b003).
A trip reset time can be selected by Reset Selection (C102). In addition, the reset signal can
be applied only to trip reset due to an error.
For the Reset (RS) terminal, only the NO contact setting is effective.
Do not use the reset terminal to stop the Inverter output. The reset operation will clear various data
such as electronic thermal function and usage rate counter for regenerative braking, thereby
causing damage to the Inverter.
Parameter
No.
b003
b007
b028
b029
b030
C102
SYSDRIVE MX2 Series USER'S MANUAL (3G3MX2-A@@@@)
Function name
Data
Restart Standby
0.3 to
Time
100.0
Frequency
0.00 to
Matching Lower
400.0
Limit Frequency
(1000.)
Setting
0.20 ×
Rated
Frequency Pull-
current to
2.00 ×
in Restart Level
Rated
current
Frequency Pull-
0.1 to
in Restart
3000.
Parameter
Starting
00
Frequency at
01
Frequency Pull-
in Restart
02
Selection
00
Reset Selection
01
02
5-8 Restart Functions
Description
Time from reset to restart
If the frequency drops to the set
frequency or below during the motor free
run, the Inverter restarts at 0 Hz.
Current limit level at frequency pull-in
restart
Frequency reduction time at frequency
pull-in restart
Frequency at interruption
Maximum frequency
Set frequency
Trip reset at power-on (example 1)
Normal: Output shut off
Abnormal: Trip reset
Trip reset at power-off (example 2)
Normal: Output shut off
Abnormal: Trip reset
Trip reset at power-on (example 1)
Normal: Disabled
Abnormal: Trip reset
Default
Unit
5
setting
1.0
s
0.00
Hz
Inverter
rated
A
current
0.5
s
00
00
5-100