Preparing for Operation
n039

Multi-function Input 5 (S6)

Setting range
2 to 25
Set Values
Set value
0
Reverse rotation/Stop (2-wire sequence)
1
Stop command (3-wire sequence). S3 will be used for the forward/reverse rotation command
and the value set with n036 will be ignored.
9
Multi-step speed command 1
10
Multi-step speed command 2
11
Inching command
12
Acceleration/Deceleration time switching command
D Example of Wiring for 2-wire Sequential Operation (Set Value: 0)
D Example of Wiring for 3-wire Sequential Operation (Set Value: 1)
D Example of Multi-step Operation (Set Values: 9 and 10)
Select multi-step speed command 1 for the Inverter in two-step speed operation and multi-step speed
commands 1 and 2 for the Inverter in four-step speed operation.
Forward
rotation/Stop
Multi-step speed
command 1
Multi-step speed
command 2
3-18
Unit
Operation switch
Stop switch
(NO)
(NC)
Frequency
reference
Frequency
reference 1
---
Description
Forward rotation/Stop
Reverse rotation/Stop
Run command (Operates when the
operation switch is closed)
Stop command (Stops when the stop
switch is open)
Forward/Reverse rotation command
Frequency
reference 4
Frequency
reference 3
Frequency
reference 2
Chapter 3
Default setting
10

Hide quick links:

Advertisement

Table of Contents
loading